Data CenterS24
CRAC/CRAH Monitoring
Bài toán
Precision air conditioners alarm locally on their own display, so a failed compressor or a high-pressure trip is noticed only when hall temperature rises.
Tổng quan giải pháp
MILESGO gateways collect data from CRAC / CRAH precision air conditioners, temperature and humidity sensors, water leak detection controllers over Modbus RTU / BACnet MS/TP / SNMP, and deliver it to the DCIM, the BMS, SMS, email and messaging alarms as SNMP / BACnet/IP / MQTT. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.
Typical scope
- CRAC / CRAH precision air conditioners
- temperature and humidity sensors
- water leak detection controllers
Protocol path
Modbus RTU / BACnet MS/TP / SNMP → SNMP / BACnet/IP / MQTT
Implementation checklist for the project manager
- Collect register maps and protocol documents from every equipment vendor early; a missing map is the most common delay.
- Devices on one serial channel must share protocol and communication parameters; group them per channel at design time.
- Collect MIB files, SNMP versions and v3 credentials for every UPS / PDU / cooling model.
- Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
- Commission in read-only mode first; enable write / control points only after the client approves each one.
- Hand over configuration backups, point table, IP plan and as-built drawings, with a short operator training.
Project deliverables
- Signed point table and protocol mapping
- Gateway configuration files and backups
- IP address plan and network drawing
- FAT and SAT test records
- As-built documentation and operator training
Kiến trúc hệ thống
Field layer: CRAC / CRAH precision air conditioners, temperature and humidity sensors, water leak detection controllers, connected over Modbus RTU / BACnet MS/TP / SNMP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the DCIM, the BMS, SMS, email and messaging alarms, which receives the data as SNMP / BACnet/IP / MQTT. Remote access for maintenance runs over VPN rather than open internet ports.
Thành phần hệ thống
- Field devices
- CRAC / CRAH precision air conditioners, temperature and humidity sensors, water leak detection controllers
- Edge / integration
- MILESGO protocol gateways and edge controllers
- Upper systems
- the DCIM, the BMS, SMS, email and messaging alarms (SNMP / BACnet/IP / MQTT)
- Tools and commissioning
- Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools
Năng lực phần mềm và AI
- Anomaly detection on trend dataTrong lộ trình
- Predictive maintenance indicators from equipment trendsTrong lộ trình
Các bước triển khai
- 1
Site survey and point list
Inventory devices, protocols, register maps, panel space, power and network paths.
- 2
Design and point table sign-off
Map every point to the target protocol and system; agree it with the client and the upper-system contractor.
- 3
Configuration and FAT
Build the gateway configuration off site, simulate it and test against the signed point table.
- 4
Installation and wiring
Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.
- 5
SAT and alarm tests
Verify values against local readings, test every alarm and command end to end.
- 6
Handover and support
Hand over configuration backups, point table and as-built documents; train operators.
Giá trị cho khách hàng
- Alarms reach the right person by SMS, email or messaging apps
- Abnormal conditions seen early, before they become failures
- One view of all subsystems instead of separate vendor consoles
- Monitoring added without changing existing control programs