CRAC/CRAH Monitoring

Problem

Precision air conditioners alarm locally on their own display, so a failed compressor or a high-pressure trip is noticed only when hall temperature rises.

Opis rozwiązania

MILESGO gateways collect data from CRAC / CRAH precision air conditioners, temperature and humidity sensors, water leak detection controllers over Modbus RTU / BACnet MS/TP / SNMP, and deliver it to the DCIM, the BMS, SMS, email and messaging alarms as SNMP / BACnet/IP / MQTT. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.

Typical scope

  • CRAC / CRAH precision air conditioners
  • temperature and humidity sensors
  • water leak detection controllers

Protocol path

Modbus RTU / BACnet MS/TP / SNMP → SNMP / BACnet/IP / MQTT

Implementation checklist for the project manager

  • Collect register maps and protocol documents from every equipment vendor early; a missing map is the most common delay.
  • Devices on one serial channel must share protocol and communication parameters; group them per channel at design time.
  • Collect MIB files, SNMP versions and v3 credentials for every UPS / PDU / cooling model.
  • Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
  • Commission in read-only mode first; enable write / control points only after the client approves each one.
  • Hand over configuration backups, point table, IP plan and as-built drawings, with a short operator training.

Project deliverables

  • Signed point table and protocol mapping
  • Gateway configuration files and backups
  • IP address plan and network drawing
  • FAT and SAT test records
  • As-built documentation and operator training

Architektura systemu

Field layer: CRAC / CRAH precision air conditioners, temperature and humidity sensors, water leak detection controllers, connected over Modbus RTU / BACnet MS/TP / SNMP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the DCIM, the BMS, SMS, email and messaging alarms, which receives the data as SNMP / BACnet/IP / MQTT. Remote access for maintenance runs over VPN rather than open internet ports.

Skład systemu

Field devices
CRAC / CRAH precision air conditioners, temperature and humidity sensors, water leak detection controllers
Edge / integration
MILESGO protocol gateways and edge controllers
Upper systems
the DCIM, the BMS, SMS, email and messaging alarms (SNMP / BACnet/IP / MQTT)
Tools and commissioning
Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools

Możliwości oprogramowania i AI

  • Anomaly detection on trend dataW planach
  • Predictive maintenance indicators from equipment trendsW planach

Etapy wdrożenia

  1. 1

    Site survey and point list

    Inventory devices, protocols, register maps, panel space, power and network paths.

  2. 2

    Design and point table sign-off

    Map every point to the target protocol and system; agree it with the client and the upper-system contractor.

  3. 3

    Configuration and FAT

    Build the gateway configuration off site, simulate it and test against the signed point table.

  4. 4

    Installation and wiring

    Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.

  5. 5

    SAT and alarm tests

    Verify values against local readings, test every alarm and command end to end.

  6. 6

    Handover and support

    Hand over configuration backups, point table and as-built documents; train operators.

Korzyści dla klienta

  • Alarms reach the right person by SMS, email or messaging apps
  • Abnormal conditions seen early, before they become failures
  • One view of all subsystems instead of separate vendor consoles
  • Monitoring added without changing existing control programs