Medical Gas Monitoring
Il problema
Oxygen, vacuum and medical air alarm panels sound locally on each ward, and engineering finds out about a pressure drop from a nurse’s phone call.
Panoramica della soluzione
MILESGO gateways collect data from medical gas alarm panels and pressure switches, pressure transmitters, run/stop and fault dry contacts over Modbus RTU, and deliver it to the BMS, SMS, email and messaging alarms as BACnet/IP / MQTT / Modbus TCP. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.
Typical scope
- medical gas alarm panels and pressure switches
- pressure transmitters
- run/stop and fault dry contacts
Protocol path
Modbus RTU → BACnet/IP / MQTT / Modbus TCP
Implementation checklist for the project manager
- Monitoring does not replace certified medical or safety alarm systems; keep them in place and treat MILESGO data as supervisory.
- For hard-wired signals, list each DI/DO/AI/AO with its type (dry contact, 4–20 mA, 0–10 V, PT1000) and choose I/O modules accordingly.
- Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
- Commission in read-only mode first; enable write / control points only after the client approves each one.
- Confirm DIN-rail space and a stable 12–24 V supply in each panel; use UPS-backed power for critical monitoring.
- Agree data retention and the report format needed for audits with the quality team at the start.
Project deliverables
- Signed point table and protocol mapping
- Gateway configuration files and backups
- IP address plan and network drawing
- FAT and SAT test records
- As-built documentation and operator training
Architettura del sistema
Field layer: medical gas alarm panels and pressure switches, pressure transmitters, run/stop and fault dry contacts, connected over Modbus RTU. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the BMS, SMS, email and messaging alarms, which receives the data as BACnet/IP / MQTT / Modbus TCP. Remote access for maintenance runs over VPN rather than open internet ports.
Composizione del sistema
- Field devices
- medical gas alarm panels and pressure switches, pressure transmitters, run/stop and fault dry contacts
- Edge / integration
- MILESGO protocol gateways and edge controllers
- Upper systems
- the BMS, SMS, email and messaging alarms (BACnet/IP / MQTT / Modbus TCP)
- Tools and commissioning
- Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools
Funzionalità software e IA
- Anomaly detection on trend dataIn roadmap
Fasi di realizzazione
- 1
Site survey and point list
Inventory devices, protocols, register maps, panel space, power and network paths.
- 2
Design and point table sign-off
Map every point to the target protocol and system; agree it with the client and the upper-system contractor.
- 3
Configuration and FAT
Build the gateway configuration off site, simulate it and test against the signed point table.
- 4
Installation and wiring
Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.
- 5
SAT and alarm tests
Verify values against local readings, test every alarm and command end to end.
- 6
Handover and support
Hand over configuration backups, point table and as-built documents; train operators.
Valore per il cliente
- Alarms reach the right person by SMS, email or messaging apps
- Timestamped records for compliance and reporting
- Monitoring added without changing existing control programs
- One view of all subsystems instead of separate vendor consoles