MILESGO
Yêu cầu báo giá

Hospitality, Retail & CommercialS83

Hotel HVAC Energy Management

Bài toán

HVAC is the largest energy use in a hotel, yet chiller plant, VRF and room units are not metered or trended, so savings depend on staff remembering to switch things off.

Tổng quan giải pháp

MILESGO gateways collect data from chillers, VRV / VRF air conditioning systems, fan coil units (FCU), BTU / heat meters, electricity meters over BACnet/IP / Modbus RTU / M-Bus, and deliver it to the energy management system, the BMS, large-screen dashboards (HDMI) as BACnet/IP / MQTT. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.

Typical scope

  • chillers
  • VRV / VRF air conditioning systems
  • fan coil units (FCU)
  • BTU / heat meters
  • electricity meters

Protocol path

BACnet/IP / Modbus RTU / M-Bus → BACnet/IP / MQTT

Implementation checklist for the project manager

  • Daikin VRV systems connect through the HBS converter; for other brands confirm the manufacturer’s gateway or interface.
  • Record CT ratios, meter IDs and multipliers in the point table; wrong multipliers are the usual cause of billing errors.
  • Write the control sequence (start/stop order, interlocks, set-points, fallback on communication loss) and have it approved before programming.
  • Commission in read-only mode first; enable write / control points only after the client approves each one.
  • Agree KPI definitions (for example OEE components or kWh per unit) with operations before building dashboards.
  • Hand over configuration backups, point table, IP plan and as-built drawings, with a short operator training.

Project deliverables

  • Signed point table and protocol mapping
  • Gateway configuration files and backups
  • IP address plan and network drawing
  • FAT and SAT test records
  • As-built documentation and operator training

Kiến trúc hệ thống

Field layer: chillers, VRV / VRF air conditioning systems, fan coil units (FCU), BTU / heat meters, electricity meters, connected over BACnet/IP / Modbus RTU / M-Bus. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the energy management system, the BMS, large-screen dashboards (HDMI), which receives the data as BACnet/IP / MQTT. Remote access for maintenance runs over VPN rather than open internet ports.

Thành phần hệ thống

Field devices
chillers, VRV / VRF air conditioning systems, fan coil units (FCU), BTU / heat meters, electricity meters
Edge / integration
MILESGO protocol gateways and edge controllers
Upper systems
the energy management system, the BMS, large-screen dashboards (HDMI) (BACnet/IP / MQTT)
Tools and commissioning
Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools

Năng lực phần mềm và AI

  • Consumption baseline and deviation alertsThí điểm
  • Load and consumption forecastingTrong lộ trình

Các bước triển khai

  1. 1

    Site survey and point list

    Inventory devices, protocols, register maps, panel space, power and network paths.

  2. 2

    Design and point table sign-off

    Map every point to the target protocol and system; agree it with the client and the upper-system contractor.

  3. 3

    Configuration and FAT

    Build the gateway configuration off site, simulate it and test against the signed point table.

  4. 4

    Installation and wiring

    Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.

  5. 5

    SAT and alarm tests

    Verify values against local readings, test every alarm and command end to end.

  6. 6

    Handover and support

    Hand over configuration backups, point table and as-built documents; train operators.

Giá trị cho khách hàng

  • Consumption visible by area, system and time period
  • Reliable trend data for optimisation and fault diagnosis
  • Consumption attributable by tenant, department or cost centre
  • New equipment integrated by configuration, not custom driver development

Các giải pháp khác trong Hospitality, Retail & Commercial

Hãy cho chúng tôi biết về dự án của bạn

Gửi giao thức, số điểm dữ liệu và hệ thống đích. Một nhóm kinh doanh và kỹ thuật sẽ xem xét mọi yêu cầu.

Trao đổi về dự án