Building Energy Monitoring
Sorun
Electricity, water, gas and BTU meters are read by hand or not at all, so energy reports are late, incomplete and impossible to trace back to a system or floor.
Çözüme genel bakış
MILESGO gateways collect data from electricity meters, water meters, gas meters, BTU / heat meters, M-Bus meters over Modbus RTU / M-Bus / DL/T 645, and deliver it to the energy management system, the BMS, a cloud platform (MQTT) as BACnet/IP / MQTT / Modbus TCP. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.
Typical scope
- electricity meters
- water meters
- gas meters
- BTU / heat meters
- M-Bus meters
Protocol path
Modbus RTU / M-Bus / DL/T 645 → BACnet/IP / MQTT / Modbus TCP
Implementation checklist for the project manager
- Record CT ratios, meter IDs and multipliers in the point table; wrong multipliers are the usual cause of billing errors.
- M-Bus: check unit loads and cable length per segment; 2-wire M-Bus gateways need a 24 V DC supply.
- Configure NTP so trends, alarms and meter readings carry consistent timestamps.
- Confirm local storage so data survives network outages, and define the retention period.
- Fix a site / asset naming convention before the first site so data from all sites can be compared.
- Hand over configuration backups, point table, IP plan and as-built drawings, with a short operator training.
Project deliverables
- Signed point table and protocol mapping
- Gateway configuration files and backups
- IP address plan and network drawing
- FAT and SAT test records
- As-built documentation and operator training
Sistem mimarisi
Field layer: electricity meters, water meters, gas meters, BTU / heat meters, M-Bus meters, connected over Modbus RTU / M-Bus / DL/T 645. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the energy management system, the BMS, a cloud platform (MQTT), which receives the data as BACnet/IP / MQTT / Modbus TCP. Remote access for maintenance runs over VPN rather than open internet ports.
Sistem bileşenleri
- Field devices
- electricity meters, water meters, gas meters, BTU / heat meters, M-Bus meters
- Edge / integration
- MILESGO protocol gateways and edge controllers
- Upper systems
- the energy management system, the BMS, a cloud platform (MQTT) (BACnet/IP / MQTT / Modbus TCP)
- Tools and commissioning
- Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools
Yazılım ve yapay zekâ yetenekleri
- Consumption baseline and deviation alertsPilot
- Automatic report drafting from collected dataYol haritasında
Teslimat adımları
- 1
Site survey and point list
Inventory devices, protocols, register maps, panel space, power and network paths.
- 2
Design and point table sign-off
Map every point to the target protocol and system; agree it with the client and the upper-system contractor.
- 3
Configuration and FAT
Build the gateway configuration off site, simulate it and test against the signed point table.
- 4
Installation and wiring
Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.
- 5
SAT and alarm tests
Verify values against local readings, test every alarm and command end to end.
- 6
Handover and support
Hand over configuration backups, point table and as-built documents; train operators.
Müşteriye sağlanan değer
- Manual readings replaced by scheduled automatic collection
- Consumption visible by area, system and time period
- Consumption attributable by tenant, department or cost centre
- Timestamped records for compliance and reporting
Smart Building alanındaki diğer çözümler
Projenizi bize anlatın
Protokolleri, nokta sayısını ve hedef sistemi gönderin. Satış ve mühendislik ekibi her başvuruyu birlikte inceler.
Projenizi Görüşelim