UPS & Generator Monitoring
ปัญหา
Standby power is only tested monthly, and a UPS on bypass or a generator with low fuel is discovered when the mains fails.
ภาพรวมโซลูชัน
MILESGO gateways collect data from UPS units, generator controllers, automatic transfer switches (ATS), level sensors over SNMP / Modbus RTU / Modbus TCP, and deliver it to the BMS, the NMS (SNMP manager), SMS, email and messaging alarms as BACnet/IP / MQTT / SNMP. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.
Typical scope
- UPS units
- generator controllers
- automatic transfer switches (ATS)
- level sensors
Protocol path
SNMP / Modbus RTU / Modbus TCP → BACnet/IP / MQTT / SNMP
Implementation checklist for the project manager
- Collect MIB files, SNMP versions and v3 credentials for every UPS / PDU / cooling model.
- Collect register maps and protocol documents from every equipment vendor early; a missing map is the most common delay.
- Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
- Confirm DIN-rail space and a stable 12–24 V supply in each panel; use UPS-backed power for critical monitoring.
- Commission in read-only mode first; enable write / control points only after the client approves each one.
- Hand over configuration backups, point table, IP plan and as-built drawings, with a short operator training.
Project deliverables
- Signed point table and protocol mapping
- Gateway configuration files and backups
- IP address plan and network drawing
- FAT and SAT test records
- As-built documentation and operator training
สถาปัตยกรรมระบบ
Field layer: UPS units, generator controllers, automatic transfer switches (ATS), level sensors, connected over SNMP / Modbus RTU / Modbus TCP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the BMS, the NMS (SNMP manager), SMS, email and messaging alarms, which receives the data as BACnet/IP / MQTT / SNMP. Remote access for maintenance runs over VPN rather than open internet ports.
องค์ประกอบของระบบ
- Field devices
- UPS units, generator controllers, automatic transfer switches (ATS), level sensors
- Edge / integration
- MILESGO protocol gateways and edge controllers
- Upper systems
- the BMS, the NMS (SNMP manager), SMS, email and messaging alarms (BACnet/IP / MQTT / SNMP)
- Tools and commissioning
- Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools
ความสามารถด้านซอฟต์แวร์และ AI
- Predictive maintenance indicators from equipment trendsอยู่ในแผน
ขั้นตอนการส่งมอบ
- 1
Site survey and point list
Inventory devices, protocols, register maps, panel space, power and network paths.
- 2
Design and point table sign-off
Map every point to the target protocol and system; agree it with the client and the upper-system contractor.
- 3
Configuration and FAT
Build the gateway configuration off site, simulate it and test against the signed point table.
- 4
Installation and wiring
Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.
- 5
SAT and alarm tests
Verify values against local readings, test every alarm and command end to end.
- 6
Handover and support
Hand over configuration backups, point table and as-built documents; train operators.
คุณค่าสำหรับลูกค้า
- Alarms reach the right person by SMS, email or messaging apps
- Abnormal conditions seen early, before they become failures
- One view of all subsystems instead of separate vendor consoles
- Timestamped records for compliance and reporting