Transportation & InfrastructureS62
Railway Facility Monitoring
ปัญหา
Trackside equipment rooms, substations and station buildings along the line are unmanned, and their power, cooling and intrusion alarms reach maintenance crews late.
ภาพรวมโซลูชัน
MILESGO gateways collect data from UPS units, CRAC / CRAH precision air conditioners, electricity meters, door, intrusion and cabinet-open contacts, temperature and humidity sensors, generator controllers over Modbus RTU / Modbus TCP / SNMP, and deliver it to SCADA, the NMS (SNMP manager), SMS, email and messaging alarms as MQTT / SNMP / IEC 60870-5-104. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.
Typical scope
- UPS units
- CRAC / CRAH precision air conditioners
- electricity meters
- door, intrusion and cabinet-open contacts
- temperature and humidity sensors
- generator controllers
Protocol path
Modbus RTU / Modbus TCP / SNMP → MQTT / SNMP / IEC 60870-5-104
Implementation checklist for the project manager
- Check 4G signal and the SIM data plan at every site before committing to cellular backhaul.
- Keep OT networks segregated and use VPN for remote access instead of opening ports to the internet.
- For hard-wired signals, list each DI/DO/AI/AO with its type (dry contact, 4–20 mA, 0–10 V, PT1000) and choose I/O modules accordingly.
- Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
- Standardise one configuration template per equipment type so further sites are copied, not rebuilt.
- Fix a site / asset naming convention before the first site so data from all sites can be compared.
Project deliverables
- Signed point table and protocol mapping
- Gateway configuration files and backups
- IP address plan and network drawing
- FAT and SAT test records
- As-built documentation and operator training
สถาปัตยกรรมระบบ
Field layer: UPS units, CRAC / CRAH precision air conditioners, electricity meters, door, intrusion and cabinet-open contacts, temperature and humidity sensors, generator controllers, connected over Modbus RTU / Modbus TCP / SNMP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: SCADA, the NMS (SNMP manager), SMS, email and messaging alarms, which receives the data as MQTT / SNMP / IEC 60870-5-104. Remote access for maintenance runs over VPN rather than open internet ports.
องค์ประกอบของระบบ
- Field devices
- UPS units, CRAC / CRAH precision air conditioners, electricity meters, door, intrusion and cabinet-open contacts, temperature and humidity sensors, generator controllers
- Edge / integration
- MILESGO protocol gateways and edge controllers
- Upper systems
- SCADA, the NMS (SNMP manager), SMS, email and messaging alarms (MQTT / SNMP / IEC 60870-5-104)
- Tools and commissioning
- Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools
ความสามารถด้านซอฟต์แวร์และ AI
- Alarm noise reduction and root-cause groupingอยู่ในแผน
- Predictive maintenance indicators from equipment trendsอยู่ในแผน
ขั้นตอนการส่งมอบ
- 1
Site survey and point list
Inventory devices, protocols, register maps, panel space, power and network paths.
- 2
Design and point table sign-off
Map every point to the target protocol and system; agree it with the client and the upper-system contractor.
- 3
Configuration and FAT
Build the gateway configuration off site, simulate it and test against the signed point table.
- 4
Installation and wiring
Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.
- 5
SAT and alarm tests
Verify values against local readings, test every alarm and command end to end.
- 6
Handover and support
Hand over configuration backups, point table and as-built documents; train operators.
คุณค่าสำหรับลูกค้า
- Unattended sites supervised without permanent staff
- Alarms reach the right person by SMS, email or messaging apps
- Remote diagnosis and fewer site visits
- Configuration templates reused across sites
โซลูชันอื่นใน Transportation & Infrastructure
บอกเราเกี่ยวกับโครงการของคุณ
ส่งโปรโตคอล จำนวนจุดข้อมูล และระบบปลายทางมาให้เรา ทีมฝ่ายขายและวิศวกรรมจะตรวจสอบทุกคำขอ
ปรึกษาโครงการของคุณ