UPS & Generator Monitoring

Il problema

Standby power is only tested monthly, and a UPS on bypass or a generator with low fuel is discovered when the mains fails.

Panoramica della soluzione

MILESGO gateways collect data from UPS units, generator controllers, automatic transfer switches (ATS), level sensors over SNMP / Modbus RTU / Modbus TCP, and deliver it to the BMS, the NMS (SNMP manager), SMS, email and messaging alarms as BACnet/IP / MQTT / SNMP. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.

Typical scope

  • UPS units
  • generator controllers
  • automatic transfer switches (ATS)
  • level sensors

Protocol path

SNMP / Modbus RTU / Modbus TCP → BACnet/IP / MQTT / SNMP

Implementation checklist for the project manager

  • Collect MIB files, SNMP versions and v3 credentials for every UPS / PDU / cooling model.
  • Collect register maps and protocol documents from every equipment vendor early; a missing map is the most common delay.
  • Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
  • Confirm DIN-rail space and a stable 12–24 V supply in each panel; use UPS-backed power for critical monitoring.
  • Commission in read-only mode first; enable write / control points only after the client approves each one.
  • Hand over configuration backups, point table, IP plan and as-built drawings, with a short operator training.

Project deliverables

  • Signed point table and protocol mapping
  • Gateway configuration files and backups
  • IP address plan and network drawing
  • FAT and SAT test records
  • As-built documentation and operator training

Architettura del sistema

Field layer: UPS units, generator controllers, automatic transfer switches (ATS), level sensors, connected over SNMP / Modbus RTU / Modbus TCP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the BMS, the NMS (SNMP manager), SMS, email and messaging alarms, which receives the data as BACnet/IP / MQTT / SNMP. Remote access for maintenance runs over VPN rather than open internet ports.

Composizione del sistema

Field devices
UPS units, generator controllers, automatic transfer switches (ATS), level sensors
Edge / integration
MILESGO protocol gateways and edge controllers
Upper systems
the BMS, the NMS (SNMP manager), SMS, email and messaging alarms (BACnet/IP / MQTT / SNMP)
Tools and commissioning
Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools

Funzionalità software e IA

  • Predictive maintenance indicators from equipment trendsIn roadmap

Fasi di realizzazione

  1. 1

    Site survey and point list

    Inventory devices, protocols, register maps, panel space, power and network paths.

  2. 2

    Design and point table sign-off

    Map every point to the target protocol and system; agree it with the client and the upper-system contractor.

  3. 3

    Configuration and FAT

    Build the gateway configuration off site, simulate it and test against the signed point table.

  4. 4

    Installation and wiring

    Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.

  5. 5

    SAT and alarm tests

    Verify values against local readings, test every alarm and command end to end.

  6. 6

    Handover and support

    Hand over configuration backups, point table and as-built documents; train operators.

Valore per il cliente

  • Alarms reach the right person by SMS, email or messaging apps
  • Abnormal conditions seen early, before they become failures
  • One view of all subsystems instead of separate vendor consoles
  • Timestamped records for compliance and reporting