Data Center Cooling Monitoring

Il problema

Chillers, pumps, cooling towers and CRAH units are controlled by different contractors, so the operator cannot see the whole cooling chain or measure how much energy cooling uses.

Panoramica della soluzione

MILESGO gateways collect data from chillers, chilled water pumps, cooling towers, CRAC / CRAH precision air conditioners, BTU / heat meters, electricity meters over BACnet/IP / Modbus TCP / Modbus RTU / M-Bus, and deliver it to the DCIM, SCADA, the energy management system as OPC UA / SNMP / MQTT. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.

Typical scope

  • chillers
  • chilled water pumps
  • cooling towers
  • CRAC / CRAH precision air conditioners
  • BTU / heat meters
  • electricity meters

Protocol path

BACnet/IP / Modbus TCP / Modbus RTU / M-Bus → OPC UA / SNMP / MQTT

Implementation checklist for the project manager

  • Collect register maps and protocol documents from every equipment vendor early; a missing map is the most common delay.
  • Commission in read-only mode first; enable write / control points only after the client approves each one.
  • Record CT ratios, meter IDs and multipliers in the point table; wrong multipliers are the usual cause of billing errors.
  • Configure NTP so trends, alarms and meter readings carry consistent timestamps.
  • Agree KPI definitions (for example OEE components or kWh per unit) with operations before building dashboards.
  • Keep OT networks segregated and use VPN for remote access instead of opening ports to the internet.

Project deliverables

  • Signed point table and protocol mapping
  • Gateway configuration files and backups
  • IP address plan and network drawing
  • FAT and SAT test records
  • As-built documentation and operator training

Architettura del sistema

Field layer: chillers, chilled water pumps, cooling towers, CRAC / CRAH precision air conditioners, BTU / heat meters, electricity meters, connected over BACnet/IP / Modbus TCP / Modbus RTU / M-Bus. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the DCIM, SCADA, the energy management system, which receives the data as OPC UA / SNMP / MQTT. Remote access for maintenance runs over VPN rather than open internet ports.

Composizione del sistema

Field devices
chillers, chilled water pumps, cooling towers, CRAC / CRAH precision air conditioners, BTU / heat meters, electricity meters
Edge / integration
MILESGO protocol gateways and edge controllers
Upper systems
the DCIM, SCADA, the energy management system (OPC UA / SNMP / MQTT)
Tools and commissioning
Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools

Funzionalità software e IA

  • Anomaly detection on trend dataIn roadmap
  • Load and consumption forecastingIn roadmap

Fasi di realizzazione

  1. 1

    Site survey and point list

    Inventory devices, protocols, register maps, panel space, power and network paths.

  2. 2

    Design and point table sign-off

    Map every point to the target protocol and system; agree it with the client and the upper-system contractor.

  3. 3

    Configuration and FAT

    Build the gateway configuration off site, simulate it and test against the signed point table.

  4. 4

    Installation and wiring

    Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.

  5. 5

    SAT and alarm tests

    Verify values against local readings, test every alarm and command end to end.

  6. 6

    Handover and support

    Hand over configuration backups, point table and as-built documents; train operators.

Valore per il cliente

  • One view of all subsystems instead of separate vendor consoles
  • Consumption visible by area, system and time period
  • Reliable trend data for optimisation and fault diagnosis
  • Monitoring added without changing existing control programs