IAQ-1007-H
Gateway-Type Indoor Air Quality Sensor IAQ-1007-H
Tecnologia di base Sunfull
Indoor air quality sensors measuring PM2.5, CO2, VOC, temperature and humidity; the HMI1001-IAQ is also a gateway serving BACnet, Modbus, OPC UA and MQTT, and the IAQ-1007 series adds PM10 and formaldehyde over Modbus.
Air Quality Monitoring
Monitors PM2.5, CO2, VOC (Volatile Organic Compounds), temperature, and humidity.
Sensor as a Gateway
The sensor itself acts as a gateway, supporting data collection via BACnet and Modbus protocols, making it easy to expand (HMI1001-IAQ).
PID Control Function
Support PID control functionality for precise process control.
Protocolli e ruoli
| Protocollo | Direzione | Ruolo | Versione | Dispositivi max | Punti max |
|---|---|---|---|---|---|
| Modbus RTU | target | server | - | - | - |
Specifiche tecniche
general
- Support Protocols
- Modbus (9600,8,1,N, ID=1)
- PM2.5 Detection Range
- 0~1000ug/m3, +/-10% (@100~500ug/m3); +/-10ug/m3 (@0~100ug/m3)
- CO2 Detection Range
- 400~5000ppm, +/-(75ppm + 5% of reading)
- VOC/TVOC Detection Range
- 0~2000ppb, +/-30%FS @25C
- PM10 Detection Range
- 0~1000ug/m3, +/-10ug/m3 +/-10% (@100~500ug/m3); +/-10ug/m3 (@0~100ug/m3)
- Formaldehyde Detection Range
- 0ppb~1000ppb, +/-15%FS @25C
- Gateway Function
- -
environment
- Temperature Detection Range
- -40C to +80C, +/-0.5C (@25C); +/-0.1C (full scale)
- Humidity Detection Range
- 0%~100%RH, +/-3%RH (@25C, 30%RH~80%RH), other +/-5%RH
- Temperature
- -10C to +50C (working); -40C to +50C (storage and transportation)
- Humidity
- 0% - 95% no condensation (working)
mechanical
- Material
- Aluminum Alloy
- Installation
- Square appearance, ceiling/wall mounted
- Dimensions
- 188mm x 144.5mm x 33mm
power
- Power Supply
- DC 12~24V