MILESGO
Minta Penawaran

Healthcare & EducationS74

Medical Gas Monitoring

Masalahnya

Oxygen, vacuum and medical air alarm panels sound locally on each ward, and engineering finds out about a pressure drop from a nurse’s phone call.

Ikhtisar solusi

MILESGO gateways collect data from medical gas alarm panels and pressure switches, pressure transmitters, run/stop and fault dry contacts over Modbus RTU, and deliver it to the BMS, SMS, email and messaging alarms as BACnet/IP / MQTT / Modbus TCP. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.

Typical scope

  • medical gas alarm panels and pressure switches
  • pressure transmitters
  • run/stop and fault dry contacts

Protocol path

Modbus RTU → BACnet/IP / MQTT / Modbus TCP

Implementation checklist for the project manager

  • Monitoring does not replace certified medical or safety alarm systems; keep them in place and treat MILESGO data as supervisory.
  • For hard-wired signals, list each DI/DO/AI/AO with its type (dry contact, 4–20 mA, 0–10 V, PT1000) and choose I/O modules accordingly.
  • Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
  • Commission in read-only mode first; enable write / control points only after the client approves each one.
  • Confirm DIN-rail space and a stable 12–24 V supply in each panel; use UPS-backed power for critical monitoring.
  • Agree data retention and the report format needed for audits with the quality team at the start.

Project deliverables

  • Signed point table and protocol mapping
  • Gateway configuration files and backups
  • IP address plan and network drawing
  • FAT and SAT test records
  • As-built documentation and operator training

Arsitektur sistem

Field layer: medical gas alarm panels and pressure switches, pressure transmitters, run/stop and fault dry contacts, connected over Modbus RTU. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the BMS, SMS, email and messaging alarms, which receives the data as BACnet/IP / MQTT / Modbus TCP. Remote access for maintenance runs over VPN rather than open internet ports.

Komposisi sistem

Field devices
medical gas alarm panels and pressure switches, pressure transmitters, run/stop and fault dry contacts
Edge / integration
MILESGO protocol gateways and edge controllers
Upper systems
the BMS, SMS, email and messaging alarms (BACnet/IP / MQTT / Modbus TCP)
Tools and commissioning
Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools

Kemampuan perangkat lunak dan AI

  • Anomaly detection on trend dataDalam rencana

Langkah pelaksanaan

  1. 1

    Site survey and point list

    Inventory devices, protocols, register maps, panel space, power and network paths.

  2. 2

    Design and point table sign-off

    Map every point to the target protocol and system; agree it with the client and the upper-system contractor.

  3. 3

    Configuration and FAT

    Build the gateway configuration off site, simulate it and test against the signed point table.

  4. 4

    Installation and wiring

    Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.

  5. 5

    SAT and alarm tests

    Verify values against local readings, test every alarm and command end to end.

  6. 6

    Handover and support

    Hand over configuration backups, point table and as-built documents; train operators.

Nilai bagi pelanggan

  • Alarms reach the right person by SMS, email or messaging apps
  • Timestamped records for compliance and reporting
  • Monitoring added without changing existing control programs
  • One view of all subsystems instead of separate vendor consoles

Solusi lain di Healthcare & Education

Ceritakan proyek Anda

Kirimkan protokol, jumlah titik, dan sistem target. Tim penjualan dan teknik meninjau setiap pengajuan.

Diskusikan Proyek Anda