Factory Equipment Monitoring
Masalahnya
Supervisors learn that a machine has stopped by walking the floor, and stoppage causes are written on paper at the end of the shift.
Ikhtisar solusi
MILESGO gateways collect data from PLCs, machine HMIs and CNC controllers, run/stop and fault dry contacts, electricity meters over S7 / Modbus TCP / Modbus RTU / EtherNet/IP, and deliver it to WEB HMI panels, large-screen dashboards (HDMI), MES, SMS, email and messaging alarms as OPC UA / MQTT. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.
Typical scope
- PLCs
- machine HMIs and CNC controllers
- run/stop and fault dry contacts
- electricity meters
Protocol path
S7 / Modbus TCP / Modbus RTU / EtherNet/IP → OPC UA / MQTT
Implementation checklist for the project manager
- Do not modify validated PLC programs; read existing data areas or add gateway-side mapping instead.
- For hard-wired signals, list each DI/DO/AI/AO with its type (dry contact, 4–20 mA, 0–10 V, PT1000) and choose I/O modules accordingly.
- Agree KPI definitions (for example OEE components or kWh per unit) with operations before building dashboards.
- List dashboard users and roles, and configure user permissions accordingly.
- Define an alarm matrix (priority, recipient, escalation) and test every alarm end to end at SAT.
- Roll out in phases: pilot one site or area, confirm data quality, then replicate.
Project deliverables
- Signed point table and protocol mapping
- Gateway configuration files and backups
- IP address plan and network drawing
- FAT and SAT test records
- As-built documentation and operator training
Arsitektur sistem
Field layer: PLCs, machine HMIs and CNC controllers, run/stop and fault dry contacts, electricity meters, connected over S7 / Modbus TCP / Modbus RTU / EtherNet/IP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: WEB HMI panels, large-screen dashboards (HDMI), MES, SMS, email and messaging alarms, which receives the data as OPC UA / MQTT. Remote access for maintenance runs over VPN rather than open internet ports.
Komposisi sistem
- Field devices
- PLCs, machine HMIs and CNC controllers, run/stop and fault dry contacts, electricity meters
- Edge / integration
- MILESGO protocol gateways and edge controllers
- Upper systems
- WEB HMI panels, large-screen dashboards (HDMI), MES, SMS, email and messaging alarms (OPC UA / MQTT)
- Tools and commissioning
- Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools
Kemampuan perangkat lunak dan AI
- Configuration screens generated from a natural-language description (SCADA gateway AI assistant)Uji coba
- Anomaly detection on trend dataDalam rencana
Langkah pelaksanaan
- 1
Site survey and point list
Inventory devices, protocols, register maps, panel space, power and network paths.
- 2
Design and point table sign-off
Map every point to the target protocol and system; agree it with the client and the upper-system contractor.
- 3
Configuration and FAT
Build the gateway configuration off site, simulate it and test against the signed point table.
- 4
Installation and wiring
Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.
- 5
SAT and alarm tests
Verify values against local readings, test every alarm and command end to end.
- 6
Handover and support
Hand over configuration backups, point table and as-built documents; train operators.
Nilai bagi pelanggan
- One view of all subsystems instead of separate vendor consoles
- Alarms reach the right person by SMS, email or messaging apps
- Reliable trend data for optimisation and fault diagnosis
- Monitoring added without changing existing control programs