MILESGO
Poproś o wycenę

Industrial & ManufacturingS38

Compressed Air Monitoring

Problem

Compressors run on local pressure switches, leaks and idle running go unnoticed, and nobody knows the energy cost of a cubic metre of compressed air.

Opis rozwiązania

MILESGO gateways collect data from air compressor controllers, flow meters, pressure transmitters, dew point sensors, electricity meters over Modbus RTU / Modbus TCP, and deliver it to the energy management system, WEB HMI panels, a cloud platform (MQTT) as MQTT / OPC UA / BACnet/IP. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.

Typical scope

  • air compressor controllers
  • flow meters
  • pressure transmitters
  • dew point sensors
  • electricity meters

Protocol path

Modbus RTU / Modbus TCP → MQTT / OPC UA / BACnet/IP

Implementation checklist for the project manager

  • Collect register maps and protocol documents from every equipment vendor early; a missing map is the most common delay.
  • For hard-wired signals, list each DI/DO/AI/AO with its type (dry contact, 4–20 mA, 0–10 V, PT1000) and choose I/O modules accordingly.
  • Record CT ratios, meter IDs and multipliers in the point table; wrong multipliers are the usual cause of billing errors.
  • Agree KPI definitions (for example OEE components or kWh per unit) with operations before building dashboards.
  • Commission in read-only mode first; enable write / control points only after the client approves each one.
  • Hand over configuration backups, point table, IP plan and as-built drawings, with a short operator training.

Project deliverables

  • Signed point table and protocol mapping
  • Gateway configuration files and backups
  • IP address plan and network drawing
  • FAT and SAT test records
  • As-built documentation and operator training

Architektura systemu

Field layer: air compressor controllers, flow meters, pressure transmitters, dew point sensors, electricity meters, connected over Modbus RTU / Modbus TCP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the energy management system, WEB HMI panels, a cloud platform (MQTT), which receives the data as MQTT / OPC UA / BACnet/IP. Remote access for maintenance runs over VPN rather than open internet ports.

Skład systemu

Field devices
air compressor controllers, flow meters, pressure transmitters, dew point sensors, electricity meters
Edge / integration
MILESGO protocol gateways and edge controllers
Upper systems
the energy management system, WEB HMI panels, a cloud platform (MQTT) (MQTT / OPC UA / BACnet/IP)
Tools and commissioning
Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools

Możliwości oprogramowania i AI

  • Consumption baseline and deviation alertsPilotaż
  • Anomaly detection on trend dataW planach

Etapy wdrożenia

  1. 1

    Site survey and point list

    Inventory devices, protocols, register maps, panel space, power and network paths.

  2. 2

    Design and point table sign-off

    Map every point to the target protocol and system; agree it with the client and the upper-system contractor.

  3. 3

    Configuration and FAT

    Build the gateway configuration off site, simulate it and test against the signed point table.

  4. 4

    Installation and wiring

    Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.

  5. 5

    SAT and alarm tests

    Verify values against local readings, test every alarm and command end to end.

  6. 6

    Handover and support

    Hand over configuration backups, point table and as-built documents; train operators.

Korzyści dla klienta

  • Consumption visible by area, system and time period
  • Abnormal conditions seen early, before they become failures
  • Reliable trend data for optimisation and fault diagnosis
  • Consumption attributable by tenant, department or cost centre

Więcej rozwiązań w obszarze Industrial & Manufacturing

Opowiedz nam o swoim projekcie

Prześlij protokoły, liczbę punktów i system docelowy. Każde zgłoszenie analizuje zespół handlowo-inżynierski.

Omów swój projekt