District Cooling Monitoring

Masalahnya

The district cooling plant must bill each customer building by energy delivered, but BTU meters in energy transfer stations are read by hand and supply temperatures are not tracked.

Ikhtisar solusi

MILESGO gateways collect data from BTU / heat meters, chillers, chilled water pumps, pressure transmitters, PT100 / PT1000 temperature probes over M-Bus / Modbus RTU / Modbus TCP / BACnet/IP, and deliver it to SCADA, the billing system, the energy management system as OPC UA / MQTT / BACnet/IP. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.

Typical scope

  • BTU / heat meters
  • chillers
  • chilled water pumps
  • pressure transmitters
  • PT100 / PT1000 temperature probes

Protocol path

M-Bus / Modbus RTU / Modbus TCP / BACnet/IP → OPC UA / MQTT / BACnet/IP

Implementation checklist for the project manager

  • M-Bus: check unit loads and cable length per segment; 2-wire M-Bus gateways need a 24 V DC supply.
  • Record CT ratios, meter IDs and multipliers in the point table; wrong multipliers are the usual cause of billing errors.
  • Configure NTP so trends, alarms and meter readings carry consistent timestamps.
  • Agree data retention and the report format needed for audits with the quality team at the start.
  • Check 4G signal and the SIM data plan at every site before committing to cellular backhaul.
  • Commission in read-only mode first; enable write / control points only after the client approves each one.

Project deliverables

  • Signed point table and protocol mapping
  • Gateway configuration files and backups
  • IP address plan and network drawing
  • FAT and SAT test records
  • As-built documentation and operator training

Arsitektur sistem

Field layer: BTU / heat meters, chillers, chilled water pumps, pressure transmitters, PT100 / PT1000 temperature probes, connected over M-Bus / Modbus RTU / Modbus TCP / BACnet/IP. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: SCADA, the billing system, the energy management system, which receives the data as OPC UA / MQTT / BACnet/IP. Remote access for maintenance runs over VPN rather than open internet ports.

Komposisi sistem

Field devices
BTU / heat meters, chillers, chilled water pumps, pressure transmitters, PT100 / PT1000 temperature probes
Edge / integration
MILESGO protocol gateways and edge controllers
Upper systems
SCADA, the billing system, the energy management system (OPC UA / MQTT / BACnet/IP)
Tools and commissioning
Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools

Kemampuan perangkat lunak dan AI

  • Load and consumption forecastingDalam rencana
  • Anomaly detection on trend dataDalam rencana

Langkah pelaksanaan

  1. 1

    Site survey and point list

    Inventory devices, protocols, register maps, panel space, power and network paths.

  2. 2

    Design and point table sign-off

    Map every point to the target protocol and system; agree it with the client and the upper-system contractor.

  3. 3

    Configuration and FAT

    Build the gateway configuration off site, simulate it and test against the signed point table.

  4. 4

    Installation and wiring

    Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.

  5. 5

    SAT and alarm tests

    Verify values against local readings, test every alarm and command end to end.

  6. 6

    Handover and support

    Hand over configuration backups, point table and as-built documents; train operators.

Nilai bagi pelanggan

  • Manual readings replaced by scheduled automatic collection
  • Consumption attributable by tenant, department or cost centre
  • Consumption visible by area, system and time period
  • Timestamped records for compliance and reporting