Chiller Plant Optimization
The problem
Chillers, chilled and condenser water pumps and cooling towers run on fixed schedules with no measured cooling output, so nobody can tell how efficiently the plant performs or where to start optimising.
Solution overview
MILESGO gateways collect data from chillers, chilled water pumps, condenser water pumps, cooling towers, BTU / heat meters, variable frequency drives (VFD), electricity meters over Modbus RTU / Modbus TCP / BACnet/IP / M-Bus, and deliver it to the BMS, the energy management system, WEB HMI panels as BACnet/IP / MQTT / OPC UA. Field equipment keeps its own protocol and control logic; integration is done by configuration and point mapping, not custom code.
Typical scope
- chillers
- chilled water pumps
- condenser water pumps
- cooling towers
- BTU / heat meters
- variable frequency drives (VFD)
- electricity meters
Protocol path
Modbus RTU / Modbus TCP / BACnet/IP / M-Bus → BACnet/IP / MQTT / OPC UA
Implementation checklist for the project manager
- Collect register maps and protocol documents from every equipment vendor early; a missing map is the most common delay.
- Write the control sequence (start/stop order, interlocks, set-points, fallback on communication loss) and have it approved before programming.
- Commission in read-only mode first; enable write / control points only after the client approves each one.
- Record CT ratios, meter IDs and multipliers in the point table; wrong multipliers are the usual cause of billing errors.
- M-Bus: check unit loads and cable length per segment; 2-wire M-Bus gateways need a 24 V DC supply.
- Build and simulate the configuration off site (FAT) before installation to shorten time on site.
- Configure NTP so trends, alarms and meter readings carry consistent timestamps.
Project deliverables
- Signed point table and protocol mapping
- Gateway configuration files and backups
- IP address plan and network drawing
- FAT and SAT test records
- As-built documentation and operator training
System architecture
Field layer: chillers, chilled water pumps, condenser water pumps, cooling towers, BTU / heat meters, variable frequency drives (VFD), electricity meters, connected over Modbus RTU / Modbus TCP / BACnet/IP / M-Bus. Edge and integration layer: MILESGO protocol gateways and edge controllers, mounted on DIN rail in existing panels, polling each device, time-stamping values and buffering them locally. Upper layer: the BMS, the energy management system, WEB HMI panels, which receives the data as BACnet/IP / MQTT / OPC UA. Remote access for maintenance runs over VPN rather than open internet ports.
System composition
- Field devices
- chillers, chilled water pumps, condenser water pumps, cooling towers, BTU / heat meters, variable frequency drives (VFD), electricity meters
- Edge / integration
- MILESGO protocol gateways and edge controllers
- Upper systems
- the BMS, the energy management system, WEB HMI panels (BACnet/IP / MQTT / OPC UA)
- Tools and commissioning
- Web-based configuration, point table import/export (Excel), off-site simulation and on-site diagnostic tools
Software and AI capabilities
- Consumption baseline and deviation alertsPilot
- Load and consumption forecastingRoadmap
- Anomaly detection on trend dataRoadmap
Delivery steps
- 1
Site survey and point list
Inventory devices, protocols, register maps, panel space, power and network paths.
- 2
Design and point table sign-off
Map every point to the target protocol and system; agree it with the client and the upper-system contractor.
- 3
Configuration and FAT
Build the gateway configuration off site, simulate it and test against the signed point table.
- 4
Installation and wiring
Mount gateways on DIN rail, wire RS-485 / I/O / Ethernet, apply the IP plan.
- 5
SAT and alarm tests
Verify values against local readings, test every alarm and command end to end.
- 6
Handover and support
Hand over configuration backups, point table and as-built documents; train operators.
Customer value
- Consumption visible by area, system and time period
- Reliable trend data for optimisation and fault diagnosis
- Monitoring added without changing existing control programs
- Abnormal conditions seen early, before they become failures
More solutions in Smart Building
Tell us about your project
Send the protocols, point count and target system. A sales and engineering pair reviews every submission.
Discuss Your Project