MILESGO
Request a Quote

HMI1010-MBus

MBus to MQTT Gateway HMI1010-MBus

Core technology by Sunfull

Connects two-wire and four-wire M-Bus meters (water, energy and heat meters) and Modbus devices to BACnet, Modbus, MQTT and OPC UA head-end systems.

Protocols and roles

ProtocolDirectionRoleVersionMax devicesMax points
M-Bussourcemaster--256
Modbus TCPtargetserver--256
DL/T 645sourceclient--256
BACnet/IPtargetserver--256
MQTTtargetpublisher--256
OPC UAtargetserver--256

Specifications

general

OS
Linux
Ethernet Ports
1x 10M/100M NIC
Collection Protocols
MBus_WaterMeter (CJ188), MBus_EnergyMeter (CJ188), MBus_EnergyMeter_EN (EN1434), ModbusTCPClient, DLT645-1997, DLT645-2007
Transfer Protocols
Modbus TCP, BACnet IP, MQTT, OPC UA
Serial Ports
-
MBus
One MBus bus (M+, M-); up to 32 devices
MBus Static Voltage
20V~24V DC
MBus Send Voltage
30V~36V DC

performance

CPU
1 Core 750MHz
RAM
64M
Load Capacity
200 standard loads (1.5 mA)
Support Tags
256

power

Power
6W
Power Supply
DC 24V

mechanical

Dimensions
119mm x 55mm x 33mm
Weight
210g
Material
Galvanized Steel
Installation
DIN-Rail / Wall-mounted

environment

Temperature
-20C to +70C (working); -30C to +75C (storage and transportation)
Humidity
20% - 90% no condensation (working); 15% - 95% no condensation (storage and transportation)